Publication CIG-WD001A-EN-P - October 2003
5-10 1756 ControlLogix I/O Modules
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non-isol ated
wir ing
Isolate d wiri ng
1. All terminals with the same name are connected together on the module. For
example, L2 can be connected to either terminal marked L2-15.
2. When you use the second L2-15 terminal to daisy chain to other RTBs, always
connect the daisy chain to the terminal directly connected to the supply wire, as
shown in the example above.
3. If separate power sources are used, do not exceed the specified isolation voltage.
Daisy chain to other RTBs
L2-0
L2-0
L2-1
L2-2
L2-3
L2-8
L2-4
L2-5
L2-6
L2-7
Not used
L2-9
L2-10
L2-11
L2-12
L2-13
L2-14
L2-15
L2-15
IN-0
IN-1
IN-2
IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not used
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not used
L2-2
L2-4
L2
L1
L1-0
L1-2
L1-4
Jumper bar
(Cut to length)
NOTES:
Do not connect more than 2 wires to any single terminal.
1756-IM16I
12
34
5
6
7
8
910
11
12
1314
1516
1718
19
20
1. All terminals with the same name are connected together on the module.For example,
L2 can be connected to any terminal marked L2-0.
2. When you daisy chain from a group to another RTB, always connect the daisy chain to
the terminal directly connected to the supply wire, as shown above.
3. This wiring example shows a s ingle voltage source.
4. If separate power sources are used, do n ot exceed the specified isolation voltage.
Daisy chain to other RTBs
Group 0Group 0
Group 1Group 1
IN-1
IN-3
IN-5
IN-7
L2-0
IN-9
IN-11
IN-13
IN-15
L2-1
IN-0
IN-2
IN-4
IN-6
L2-0
IN-8
IN-10
IN-12
IN-14
L2-1
L2
L1
NOTES:
5. Do not connect more than 2 wires to any single terminal.
1756-IN16
12
34
56
78
910
1112
1314
1516
1718
1920
3-Wire RTD
Shield Ground
IN-1/A
IN-1/B
RTN-1/C
IN-3/A
IN-3/B
RTN-3/C
Not used
IN-5/A
IN-5/B
RTN-5/C
IN-0/A
IN-0/B
RTN-0/C
IN-2/A
IN-2/B
RTN-2/C
Not used
IN-4/A
IN-4/B
RTN-4/C
1. For 2-wire resistor applications, including calibration, make sure IN-x/B and
RTN-x/C are shorted together. The example above shows IN-4/B and RTN-4/C
shorted together.
2-Wire RTD
NOTES:
2. Do not connect more than 2 wires to any single terminal.
12
34
56
78
910
1112
1314
1516
1718
1920
1. Wiring is exactly the same as the 3-wire RTD with one wire left open.
4-Wire RTD
Shield Ground
IN-1/A
IN-1/B
RTN-1/C
IN-3/A
IN-3/B
RTN-3/C
Not used
IN-5/A
IN-5/B
RTN-5/C
IN-0/A
IN-0/B
RTN-0/C
IN-2/A
IN-2/B
RTN-2/C
Not used
IN-4/A
IN-4/B
RTN-4/C
NOTES:
2. Do not connect more than 2 wires to any single terminal.
1756-IR6I – 2 or 3-Wire RTD
1756-IR6I – 4-Wire RTD