OMRON Tech Note
Setting up AB Point I/O with CS1W-DRM21 2/19
Step 1 The Hardware
• Set the1734-ADN thumbwheel for Node # (for this example, use 01)
• Mount the needed I/O Slices to the 1734-ADN Adapter
• Either supply an external 24vDC supply for the Adapter, or jumper from
the DeviceNet connector
• Set the DRM21 Unit # (for this example, use 3)
• Set the DRM21 Node # (for this example, use 60)
• Set the DRM21 DIP switches to all OFF (125K baud)
• Mount the module on the backplane of the CS1
• Wire the network with ODVA approved cable such as Belden #3084A
• Make sure that two terminating resistors are used (one at each end of the
trunk)
• Apply 24vDC to the red and black terminals of one of the DeviceNet
connectors
• Allow at least 40 seconds for the 1734 to power-up and stabilize before
proceeding