CalAmpWirelessNetworksTechnicalSupport|Tel507.833.8819|Email[email protected] Page5of10
aresentforeachcloseandreopenoftheTCPconnection.Thisaddsalotofonairtrafficandimpactsthesystem
performance.
NotewhenusingdifferentinactivitytimeoutvaluesformessageswiththesameTCPconnection:
WhendifferentmessagesforthesameremotesharethesameTCPconnection,
eachdifferentmessage’sinactivitytimeout
wouldrestartthetimeouttimer.Messageexample:msg1inactivity60,msg2inactivity100,msg3inactivity30.These
messagesarethensentasfollows:msg1issent,msg2issent,msg3andthenawaitisdone.Sincethelastmessagewas
msg3withinactivitytimeout
of30seconds,theTCPconnectionwouldcloseafter30secondsofmsg3.
Settingexampleusingcustominactivitytimeout(100sec).
SummaryonTCPconnectiontimeout(inactivitysetting)
SincethelongestinactivitytimeoutperTCPconnectionwitharemoteunit(PLC/RTU)is120seconds(basedonmessage
inactivitymaxof120seconds),itisimportantthateachremote(PLC/RTU)ispolledwiththe120secondperiodtoavoid
extratrafficresultingfromadditionalTCP/IPopenandcloseconnection
messages.Forsystemswherepollingisdone
infrequently(>120sec)theadditionalTCPtrafficneedstobeconsideredforthesystemtrafficplan.
Fornormaloperationtheinactivitytimeoutdoesnotneedtobespecifiedinthe“Path”setting.Masterandremotesshould
besetthisway,especiallyifremote
PLCssendunsolicitedmessagesorinitiatecommunicationwithotherremotes.Ifa
systemhasamixofPLCs(CompactLogix/ControlLogixwithMicroLogix/SLC),thenalsorefertoCalAmp’s“AllenBradleyPLC
forViperSystem”supportbulletinavailableonCalAmp’sWEBsiteundersupport.
