CalAmpWirelessNetworksTechnicalSupport|Tel507.833.8819|Email[email protected] Page8of10
SummaryofConnectedorUnconnectedoperation
With“Connected”optionselectedandpollingintervalbetweenMessagesforthesameremoteCIPconnectionislonger
thanthe“UnconnectedTimeout”(default30seconds),“CIPForwardOpen”and“CIPForwardClose”messagesadd4extra
onairmessages(includesmsgreply)foreachunitpolled.Ifeachpollis2messages
(msgandreply)the4extramessages
increasethemessageload(onair)by200%.
Therefore"Connected"checkboxshouldbeunchecked(Unconnected)toavoidsending)“CIPForwardOpen”and“CIP
ForwardClose”messages.If“Connected”isrequiredthenincreasethe“UnconnectedTimeout”and“ConnectionRate”
timeouttoavaluegreaterthanthepolling
intervalperremote(useprecautionwiththis).
TimeoutsusedformessageresponsesoverEtherNet/IP“Connected”or“Unconnected”shouldnotbetooshort,therefore
shouldnotbesetlowerthan15sec(normally)intheeventitisrequiredbeinglowerthan30secforapplicationlevel
retransmission.TheTCP/IPcommunication
driverdoesitsownretransmissionsandwillnotrequireapplication
retransmissionsofmessagessinceaTCPconnectionwillnotlooseamessageunlesstheconnectionterminatesnormallyor
duetoaproblem.ThereforewithTCPlongertimeoutswithinreasonareok.Longertimeouts(ex30sec)areoksincethey