Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Configure POINT I/O Modules for DeviceNet Networks 209
The Groups pull-down includes the following:
All parameters
I/O
Configure
POINTBus
To complete entries from the Device Parameters dialog, use this procedure.
1. From the General Parameters dialog, at the groups list Select
Configuration and the parameters you want.
2. From the Device Parameters dialog, select Single and change or configure
parameters one at a time, or select All to change all selections at once.
Note that if autobaud is selected, the communication rate of this module
automatically matches the communication rate of the existing devices on