Install the ArmorPoint DeviceNet Adapters
This chapter describes how to install and wire your adapter.
Mount the Adapter and
I/O Base
To mount the ArmorPoint adapter on a wall or panel, use the screw
holes provided in the adapter.
A mounting illustration for the ArmorPoint adapter with I/O bases is
shown below.
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension
drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping
screws.
3. Mount the adapter and I/O bases using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O
base. (The ground lug connection is also a mounting hole.)
See the following sections: Page:
Mount the Adapter and I/O Base 1-1
Set the Node Address 1-2
Wire the DeviceNet Adapters 1-3
Chapter Summary and What’s Next 1-4
43769
4.02 in.
102 mm
1.81 in.
46 mm
Adapter
47.2 mm
50 mm
22 mm
50 mm
22 mm
50 mm
Drilling Dimension Drawing