Allen-Bradley 2-D Manual do Utilizador Página 79

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 172
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 78
Programming
5-10
Setup Group (continued)
[Ba
s
e
F
re
qu
e
ncy
]
Parameter # 17 Factory Default 60 Hz
[Ba
s
e
F
re
qu
e
ncy
]
Parameter Type Read & Write Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz Maximum 400 Hz
[Ba
s
e
Vol
tage]
Parameter # 18 Factory Default Max. Drive Rated Volts
[Ba
s
e
Vol
tage]
Parameter Type Read & Write Minimum 25% of Max. Drive Rated Volts
This value should be set to the motor nameplate Rated
Voltage.
Units 1 Volt Maximum 100% of Max. Drive Rated Volts
[Max
imum Vol
tage]
Parameter # 20 Factory Default Max. Drive Rated Volts
[Max
imum Vol
tage]
Parameter Type Read & Write Minimum 25% of Max. Drive Rated Voltage
This parameter sets the highest voltage the drive will
output.
Units 1 Volt Maximum 110% of Max. Drive Rated Volts
[M
inimum F
re
q
]
Parameter # 16 Factory Default 0 Hz
[M
inimum F
re
q
]
Parameter Type Read & Write Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output.
Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq].
Units 1 Hz Maximum 120 Hz
Important: This parameter can not be
programmed while the drive is running.
Vista de página 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 171 172

Comentários a estes Manuais

Sem comentários